Appendix C: NFPA Standard-Specific Requirements

The MS-9050UD has been designed for use in commercial, industrial and institutional applications
and meets the requirements for service under the National Fire Protection Association (NFPA)
Standards outlined in this Appendix. The minimum system components required for compliance
with the appropriate NFPA standard are listed below:

MS-9050UD Control Panel

Contains the main control board, cabinet (backbox and door), main power supply transformer and
power supply.

Batteries

Refer to “Power Supply Calculations” on page 153, for Standby Power Requirements.

Initiating Devices

Connected to one of the control panel's Initiating Device Circuits

Notification Appliances

Connected to the control panel's Notification Appliance Circuits via a control module.

The additional equipment listed below is needed for compliance with the NFPA 72 standards:

NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:

NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station
Service

Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed
Central Station DACR or Protected Premises Receiving Unit. This unit must be installed
as outlined in “Digital Alarm Communicator/Transmitter” on page 17.

OR

4XTMF Transmitter Module for connection to the Fire-Lite RS82 Remote Station
Receiver. See Figure C.2, “Remote Station Connection Using 4XTMF Module,” on page
166, for in
stallation instructions for this unit.

NFPA 72 Auxiliary Fire Alarm System

4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled “4XTMF Transmitter Module Installa-
tion” on page 33 and
as outlined in Figure C.1, “Municipal Box Connected to 4XTMF Transmitter
Module,” on page 165.

NFPA 72 Proprietary Fire Alarm System

MS-9050UD Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure
C.3, “Proprietary Protective Signaling System,” on page 167, for in
stallation instructions for this
unit.