NFPA Standard-Specific Requirements

NFPA 72 Proprietary Protective Signaling Systems

Figure C.3 Proprietary Protective Signaling System

Form-C relay contact
programmed to activate on
Supervisory condition.

Form-C Trouble contact which
will automatically activate on
any Trouble condition.

Form-C Alarm contact
programmed to activate on
General Alarm.

MS-9050UD Main Board

MS-9050UD Addressable Fire Control Panel

Notes:
1. Connection between the MS-9050UD and the
transmitter are supervised by the transmitter.
2. This MS-9050UD/Transmitter arrangement can be
employed for NFPA 72 Proprietary Protective Signaling
System.
3. Potter Electric Model EFT-C has not been tested for UL
864 9th Edition and is for use in retrofit applications only.