3 calculating the system current draw, 1 overview, Calculating the system current draw – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 154

Advertising
background image

154

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Power Supply Calculations

Calculating the System Current Draw

7.3 Calculating the System Current Draw

7.3.1 Overview

The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 7.3 on page 155. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 7.3 on page 155. The secondary power
source (batteries) must be able to power the system during a primary power loss. To calculate the
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 7.3 on
page 155.

When calculating current draw and the battery size, note the following:

‘Primary’ refers to the main power source for the control panel

‘Secondary’ refers to the control panel’s backup batteries

All currents are given in amperes (A). Table 7.2 shows how to convert milliamperes and
microamperes to full amperes.

7.3.2 How to Use Table 7.3 to Calculate System Current Draw

Use Table 7.3 on page 155 to calculate current draws as follows:

1.

Enter the quantity of devices in all three columns.

2.

Enter the current draw where required. Refer to the Fire-Lite Device Compatibility Document
for compatible devices and their current draw.

3.

Calculate the current draws for each in all columns.

4.

Sum the total current for each column.

5.

Copy the totals from Column 2 and Column 3 to Table 7.4 on page 156.

Following are the types of current that can be entered into Table 7.3 on page 155:

Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied

Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied

Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power

To convert...

Multiply

Example

Milliamperes (mA) to amperes (A)

mA x 0.001

3 mA x 0.001 = 0.003A

Microamperes (µA) to amperes (A)

µA x 0.000001

300 µA x 0.000001 = 0.0003 A