Master Programming Level

Programming

PAS (Positive Alarm Sequence) Delay

The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following dis-
play will appear:

A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.

Pre-signal Delay

The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:

A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.

Note that detectors can be programmed for either PAS or Pre-signal operation, not both. Refer to
“Edit Detector” on page 60 for pr
ogramming details.

Waterflow Delay

A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:

A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.

TIMERS

1=PAS DELAY 000

2=PRE SIGNAL 000

3=WATERFLOW 000

Timer Screen #1

PAS DELAY

RANGE 0-180 SECONDS

PAS Delay Screen

PRESIGNAL DELAY

RANGE 0-180 SECONDS

Pre-signal Delay Screen

TIMER

1=PAS DELAY 000

2=PRE SIGNAL 000

3=WATERFLOW 000

Timer Screen #1

WATERFLOW DELAY

RANGE 0-90 SECONDS

Waterflow Delay Screen