Zones installed, Zones enabled, Zones disabled – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 79: Zone type

Advertising
background image

MS-9050 Series Manual — P/N 52413:G 4/14/2014

79

Master Programming Level

Programming

Pressing 2 will cause the display to change to Pre-signal 18 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 18 On and Pre-signal 18 Off. When Zone 18 is pro-
grammed On, a Pre-signal activation of any device will cause Zone 18 to activate. By assigning
Zone 18 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a Pre-signal condition in the control panel. Do
not assign Zone 18 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal
condition. Attempting to do so will generate an error message and will be prevented by software
checks.

Pressing 3 will cause the display to change to Two Stage 19 On. Each press of the 3 key will cause
the display to toggle between Two Stage 19 On and Two Stage 19 Off. Refer to “Two Stage Opera-
tion” on page 88
for a description of this feature.

Zones Installed

Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to
the following:

This display will show all of the zones that have been programmed into the control panel.

Zones Enabled

Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to
the following:

This display will show all of the zones that are enabled in the control panel.

Zones Disabled

Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar
to the following:

This display will show all of the zones that are disabled in the control panel.

Zone Type

Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on
the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a
screen similar to the following:

ZONE SETUP

1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zone Setup Screen #2

ZONES INSTALLED

00 01 02 03 04 05

Zones Installed Screen

ZONES ENABLED

00 01 02 04 05 06 07

08 09 10 11 12 13 14

15 16 17 18 19

Zones Enabled Screen

ZONES DISABLED

03

Zones Disabled Screen

ZONE SETUP

1=ZONE TYPES

2=ZONES AVAILABLE

3=FUTURE

Zone Setup Screen #3

ZONE TYPE PROG

1=Z00 MONITOR

2=Z01 MONITOR

3=Z02 MONITOR

Zones Installed Screen

Advertising
This manual is related to the following products: