Advertising
background image

36

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Installation

ANN-BUS Devices

3.

Secure the ANN-SEC to the circuit board with the supplied screw.

2.9 ANN-BUS Devices

Guidelines

A variety of optional annunciation devices can be connected to an ANN-BUS communication
circuit. ANN Series devices can be connected to the primary communication circuit (EIA-485)
terminals on TB3. A secondary communication circuit (EIA-485) for these devices is available
at TB1 on the ANN-SEC card.

When using one ANN-BUS circuit, up to eight (8) annunciators can be supported.

When using both ANN-BUS communication circuits, the primary circuit supports up to three
(3) annunciators and the secondary circuit supports up to (5) annunciators.
Compatible devices include:

– ANN-80 LCD Annunciator

– ANN-80C LCD Indicator (Canadian Applications)

– ANN-S/PG Serial/Parallel Printer Interface Module

– ANN-I/O LED Driver Module

– ANN-LED Annunciator Module

– ANN-RLED Annunciator Module (red alarm LEDs only)

– ANN-RLY Relay Module

– ANN-LC Lite-Connect Module

When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in
the system.

The panel is capable of operating a primary ANN-BUS (TB3) and a secondary ANN-BUS
(TB1 on ANN-SEC card) simultaneously.

2.9.1 ANN-BUS Wiring

This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).

J13

TB

1

J1

ANN-SEC

FACP Circuit Board

connector to J13 on
main circuit board

standoff and screw

Figure 2.12 Installing the ANN-SEC Option Card

9

0

50

an

ns

e

c

.w

mf

!

r

WARNING: RISK OF ELECTRICAL SHOCK
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.