Optional Modules/Accessories Installation

Installation

8.

When the installation has been completed, enable the 4XTMF module by sliding the
disconnect switch to the left.

9.

Test system for proper operation.

2.8.2 ANN-SEC Option Card

The ANN-SEC option card allows for a secondary ANN-BUS. Install the ANN-SEC as follows.

1.

Remove the chassis mounting screw to the right of TB7 and replace it with the supplied 0.5” x
4-40 male-female standoff.

2.

Install the header into J13 on the main circuit board.

Figure 2.11 4XTMF Connectors to MS-9050UD Connectors

J8 & J9 Connectors

Jumper JP2

Standoff

Standoff

4XTMF

MS-9050UD

90

50

u

d

4

x

tm

.w

mf

Jumper JP28

NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. Relay 3 at TB3 must be programmed as
a supervisory relay.
Removing the jumper from JP2 will allow the 4XTMF to generate a trouble if the supervisory
contact opens
Leaving the jumper on JP2 will prevent generation of a trouble if the supervisory contact opens