Master Programming Level

Programming

3+1, 4+1 Express, and 4+1 Standard

The information shown in Table 3.3 is automatically programmed for the Central Station phone
number Event Codes when any of these Formats are selected. Enter 0 for an Event Code Setting to
disable the report.

Event Description

Event Code Settings

Active

Restoral

PULL STATION

1

E

MON-USER-DEF-1

1

E

WATERFLOW

1

E

MON-USER-DEF-2

1

E

SMOKE (PHOTO)

1

E

DET-USER-DEF-1

1

E

SMOKE (ION)

1

E

DET-USER-DEF-2

1

E

HEAT DETECT

1

E

DET-USER-DEF-3

1

E

SMOKE DUCT-P

1

E

DET-USER-DEF-4

1

E

PHOTO W/HEAT

1

E

DET-USER-DEF-5

1

E

DUCT SUPERVISORY

8

E

DET-USER-DEF-6

8

E

PHOTO SUPERV

8

E

DET-USER-DEF-7

8

E

MONITOR

1

E

MON-USER-DEF-3

1

E

SMOKE CONVEN

1

E

MON-USER-DEF-5

1

E

HEAT CONVEN

1

E

MON-USER-DEF-6

1

E

MEDIC ALERT

0

0

MON-USER-DEF-7

0

0

HAZARD ALERT

0

0

MON-USER-DEF-8

0

0

TORNADO ALRT

0

0

MON-USER-DEF-9

0

0

TAMPER

8

E

MON-USER-DEF-11

8

E

MON SUPERVISORY

8

E

MON-USER-DEF-12

8

E

MON SUPERV AUTO

8

E

MON-USER-DEF-13

8

E

HVAC OVRRIDE

8

E

POWER MON

6

A

MON-USER-DEF-14

6

A

TROUBLE MON

POINT_FAULT code will always be transmitted

MON-USER-DEF-15

POINT_FAULT code will always be transmitted

PROCESS MON

0

0

MON-USER-DEF-16

0

0

PROCMON AR

0

0

MON-USER-DEF-17

0

0

Table 3.3 Event Codes