E.1 nac wiring, E.1: nac wiring – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 172

Advertising
background image

172

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Wire Requirements

NAC Wiring

E.1 NAC Wiring

The following table lists NAC wiring requirements for the FACP.

Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National
Electrical Code (2005 Edition) Table 8, Conductor Properties.

NAC Load

(Amps)

Max.

allowable
total loop

resistance

(ohms)

CLASS-B

Max. allowable wire pair lenth

(feet)

CLASS-A

Max. allowable wire pair length

(feet)

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

0.25

13.20

3420

2150

1350

849

1710

1075

675

425

0.5

6.60

1710

1075

675

425

855

537

337

212

0.75

4.40

1140

717

450

283

570

358

225

142

1

3.30

855

537

337

212

427

269

169

106

1.25

2.64

684

430

270

170

342

215

135

85

1.5

2.20

570

358

225

142

285

179

112

71

1.75

1.89

489

307

193

121

244

154

96

61

2

1.65

427

269

169

106

214

134

84

53

2.25

1.47

380

239

150

94

190

119

75

47

2.5

1.32

342

215

135

85

171

107

67

42

Table E.2 NAC Wiring Requirements for FACP