4 walktest, Walktest – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 122

Advertising
background image

122

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Maintenance Programming Level

able module (control module in this example) with an address of 001 on loop 1 but have not been
programmed to any input devices. Use the up and down arrow keys to view all the zones without
input assignments.

Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be
displayed:

The Zone No Output feature allows the programmer to view the zones which have not been pro-
grammed to at least one output device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able detector with an address of 001 on loop 1 but have not been programmed to any output
devices. Use the up and down arrow keys to view all the zones without output assignments.

3.7.4 Walktest

To perform a walktest, press 1 while viewing Maintenance Screen #2. The following screen will be
displayed:

The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. Pressing
1 or 2 will cause the control panel to enter Walktest Mode and will display the following screen:

From this screen, it is possible to view the walktest log, untested system points or a summary of the
addressable devices tested during the current walktest. The user can select between any of these
screens without interrupting the current walktest session. The walktest session will not end until
the Unit In Walktest screen is exited by pressing the Escape key.

Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a screen sim-
ilar to one of the following two screens to be displayed:

If there are no events in the current walktest session, the first screen will be displayed, indicating no
events have been stored in the walktest log. If any events have been stored, a screen similar to the
second will be displayed indicating the latest event. As walktest events occur, the display will
change to indicate the latest event. All stored events can be scrolled on the screen by pressing the
up or down arrow keys. To return to the first event, press the 1st Event key.

Pressing 2 for View Points while viewing the Unit In Walktest screen will display a new screen
which will show only the points that have not yet been walk tested. The up and down arrow keys
will allow viewing of all untested points. If a point is tested while it is being displayed, the screen
will update and display the next untested point. A description on the bottom of the screen will indi-

ZONES NO OUTPUT

05 07 09 10 11 1D001

PROGRAMMING

1=WALKTEST

2=SYSTEM

3=ZONE SETUP

Maintenance Screen #2

WALKTEST

1=SILENT

2=AUDIBLE

3=VIEW RESULT

Walktest Screen

UNIT IN WALKTEST

1=VIEW WALKTEST LOG

2=VIEW POINTS

3=VIEW SUMMARY

Unit In Walktest Screen

NO EVENTS IN

WALKTEST LOG

OR

ALARM: MONITOR

NORTH CLASSROOM

Z001

1015A 012310 1M006

Advertising
This manual is related to the following products: