MS-9050 Series Manual — P/N 52413:G 4/14/2014

53

ANN-BUS Devices

Installation

Wiring the ANN-LC to the MS-9050UD

Without an ANN-SEC Card

The ANN-LC connects from the MS-9050UD via ribbon cable. Using the 21” ribbon cable,
connect the MS-9050UD at J13 to J3 on the ANN-LC. Run the ribbon cable up behind the
MS-9050UD board.

ANN-LC

backbox

protrusions

Figure 2.25 Mounting the ANN-LC into the Backbox

FL

LC

m

n

tt

ab

s.w

m

f

!

WARNING: OBSERVE PROPER ALIGNMENT (RED STRIPE ON CABLE)
CONNECTING MISMATCHED PINS WILL CAUSE PERMANENT DAMAGE TO THE BOARD.
WHEN ATTACHING THE RIBBON CABLE, BE SURE IT DOES NOT GET OVERLY TWISTED.

J13

J13

J3

MS-9050UD

ANN-LC

Figure 2.26 Wiring the ANN-LC Directly to the MS-9050UD

90

50

toFL

LC

.w

m

f

Do not

Use

Observe proper alignment!
(Red stripe on cable)

!

CAUTION:

DO NOT CONNECT DOWNSTREAM DEVICES

WHEN USING THE RIBBON CABLE TO DIRECTLY CONNECT THE ANN-LC TO THE MS-9050UD,
DO NOT CONNECT ANY ANN-BUS DEVICES DOWNSTREAM FROM THE ANN-LC.