MS-9050 Series Manual — P/N 52413:G 4/14/2014

Installation

ANN-BUS Devices

2.

Connect the ANN-S/PG to the FACP as illustrated in Figure 2.16.

3.

Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)
to the module.

4.

Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to “ANN-BUS” on page 96).
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to “Auto-Configure” on page 104).

5.

Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 2.16). Only
one printer can be connected.

Specifications

Operating Voltage: 24 VDC

Current (Alarm and Standby): 45 mA

Ambient Temperature: 32

o

F to 120

o

F (0

o

C to 49

o

C)

Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)

Mounting: Surface

Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)

For indoor use in a dry location only

PRN-6F Printer Installation

When connected to the FACP via the ANN-S/PG module, the PRN prints the status changes within
the control panel and time-stamps the printout with the time of day and date that the event occurred.
It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section contains infor-
mation on connecting a printer to the control panel and setting the printer options.

Connecting PRN-6F Printer

Remote printers require a primary AC power source. If required for the fire alarm system configu-
ration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power
source (battery backup). Since a secondary power source is not provided as a standard feature, a
separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency
power supply may be used, as long as it meets the power continuity requirements of NFPA 72.
Refer to NFPA 72 for further details.

Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable.
One end of the cable will plug into the DB-25 connector on the PRN printer and the other end plugs
into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9 port on the ANN-
S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer
cable. Connect either a serial or parallel printer, but not both at the same time.

Figure 2.16 ANN-S/PG Connection to FACP

ANN-S/PG Module

MS-9050UD

Cable

Connectors

for connection

to printer

Parallel

Serial

ANN-BUS and power wiring are
supervised and power-limited

an

nsp

g

to

90

50u

d

.w

m

f

Primary

ANN-BUS