Programming

Master Programming Level

3.6.3 Zone Setup

Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as illustrated
below:

Enable

Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:

This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 19). When the second
digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z.
Another zone can then be enabled.

Disable

Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:

This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 19). When the second
digit is entered, the zone will be disabled and the cursor will return to the original position next to
the Z. Another zone can then be disabled.

Zone 17, 18, and 19

Pressing 3 for Zone 17, 18, and 19, while viewing Zone Setup Screen #1, will display the following
screen:

Zones 17, 18, and 19 can be programmed for normal zone operation or for special purpose applica-
tions. In the above illustration, the three zones are shown Off, which means they can be pro-
grammed to function in the same manner as all other zones, by assigning them to input and output
devices in the Programming Zone Assignment Screen.

Pressing 1 will cause the display to change to PAS 17 On. Each press of the 1 key will cause the
display to toggle between PAS 17 On and PAS 17 Off. When Zone 17 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 17 to activate. By
assigning Zone 17 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control
panel. Do not assign Zone 17 to a Notification Appliance Circuit when using this zone to indicate a
PAS condition. Attempting to do so will generate an error message and will be prevented by soft-
ware checks.

PROGRAMMING

1=AUTOPROGRAM

2=POINT PROGRAM

3=ZONE SETUP

Programming Screen #2

ZONE SETUP

1=ENABLE

2=DISABLE

3=ZONE 17 18 19

Zone Setup Screen #1

ZONE SETUP

1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zone Setup Screen #2

ZONE SETUP

1=ZONE TYPES

2=ZONES AVAILABLE

3=FUTURE USE

Zone Setup Screen #3

ZONE SETUP

1=ENABLE

2=DISABLE

3=ZONE 17 18 19

Zone Setup Screen #1

ZONE TO ENABLE

Z

Enable Screen

ZONE SETUP

1=ENABLE

2=DISABLE

3=ZONE 17 18 19

Zone Setup Screen #1

ZONE TO DISABLE

Z

Disable Screen

SPEC PURPOSE ZONE

1=PAS 17 OFF

2=PRE-SIGNAL 18 OFF

3=TWO STAGE 19 OFF

Zone 17, 18, and 19 Screen