4 ann-s/pg serial/parallel interface module, Ann-s/pg serial/parallel interface module – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 43

Advertising
background image

MS-9050 Series Manual — P/N 52413:G 4/14/2014

43

ANN-BUS Devices

Installation

The following table shows the ANN-80 connections to the MS-9050UD.

Programming

Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
“ANN-BUS” on page 96 in this manual for detailed programming information. Select the LCD
option for programming.

Trouble Response

If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus
Trouble
and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of an ANN-80 trouble.

To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address correspond-
ing to the address set on the ANN-80 at the FACP.

2.9.4 ANN-S/PG Serial/Parallel Interface Module

The ANN-S/PG Serial/Parallel Interface module allows the connection of a serial or parallel printer
to the FACP for a real-time log of system events, detector status reports and event history. The
module is provided with a plastic enclosure for surface mounting. Proceed with the installation as
described in the following:

1.

Ensure that all power (AC and DC) has been removed from the FACP.

MS-9050UD (TB3)

ANN-80 (TB1)

Terminal 1 GND (-)

Terminal 1 (-)

Terminal 2 PWR (+)

Terminal 2 (+)

Terminal 3 A (ANN-BUS)

Terminal 3 (A)

Terminal 4 B (ANN-BUS)

Terminal 4 (B)

Figure 2.15 ANN-80 Wiring to FACP

FACP

ANN-80

ANN-BUS and power wiring are
supervised and power-limited

Primary ANN-BUS