90

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Master Programming Level

To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can
be attached to each circuit. Following is a list of the strobes that have been tested with this FACP
and the maximum number that can be connected to each NAC. Make sure that the NAC maximum
current is not exceeded:

System Sensor: 40 Strobes

Wheelock: 25 Strobes

Gentex: 23 Strobes

Relays

Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two
main circuit board Form-C relays from the following screen:

To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that
Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The
following screen will appear for each relay to be programmed:

Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be dis-
played:

While viewing the selected screen, press the number corresponding to the desired relay type to pro-
gram the main circuit board relay. The choice will be stored in memory and the display will return
to the Relay Type Screen which will show the programmed type choice. Press the Escape key to
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.

Notes:

1.

AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the
Supervisory and/or Process Monitor type code, when activated, will automatically reset when
the corresponding condition is cleared.

2.

A relay programmed with the Silenceable Alarm type will activate upon any alarm and reset
when the alarm is cleared and/or when the Alarm Silence button is pressed.

SYSTEM SETUP

1=TIMERS

2=NAC

3=RELAYS

System Setup Screen #2

RELAYS

1=RELAY 1

2=RELAY 2

3=RELAY 3

Relays Selection Screen

RELAY #

1=TYPE

ALARM

Relay Type Screen

RELAY

1=ALARM

2=SUPERVISORY

3=SUPERVISORY AR

Relay Screen #1

RELAY

1=PROCESS MON AR

2=AC LOSS

3=HAZARD

Relay Screen #3

RELAY

1=MEDICAL

2=SILENCEABLE ALARM

Relay Screen #4

RELAY

1=TROUBLE

2=COMM FAIL

3=PROCESS MON

Relay Screen #2