Master Programming Level

Programming

Canadian Option

Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Cana-
dian requirements. The display will change to Canadian Opt. On. Each press of the 1 key will
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory default
setting is Canadian Opt. Off.

For Canadian applications, remote annunciation must be done using the secondary ANN-BUS.
The Canadian Options configures the FACP with the following as required by Canada:

The following monitor module type codes are not available:

non-latching supervisory

non-latching process monitor

non-latching drill

process monitor

hazard

tornado

medical alert

The auto-silence timer can only be set to 0 or 20 minutes.

Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications.

Positive Alarm Sequence, the Pre-Signal option, and their corresponding timers are not
available for Canadian applications.

The installer must write in the Date of Final Assembly on the Master Marking and Warranty
label located on the FACP backbox door.

Waterflow Silenceable

Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the sys-
tem for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the
display between Waterflow Sil. No and Yes. When Waterflow Sil. No is selected, all output devices
associated with a waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is
selected, all output devices associated with waterflow type input devices, will be silenceable. The
factory default setting is Waterflow Sil. No.

Lite-Connect

Pressing 3 while viewing System Setup Screen #3 will allow the programmer to configure the
system for the Lite-Connect circuit.

Pressing 1 while viewing the Lite-Connect Setup Screen will allow the programmer to enable the
Lite-Connect circuit. Select Enabled Yes if an ANN-LC has been installed and wired to the
secondary ANN-BUS. Each press of the 1 key will toggle the display between Enabled No and
Enabled Yes.

SYSTEM SETUP

1=CANADIAN OPT. OFF

2=WATERFLOW SIL. NO

3=LITE-CONNECT

System Setup Screen #3

SYSTEM SETUP

1=CANADIAN OPT. OFF

2=WATERFLOW SIL. NO

System Setup Screen #3

LITE-CONNECT

1=ENABLED YES

2=HUB MODE SETUP

3=NODE MODE SETUP

Lite-Connect Setup Screen