Installation

ANN-BUS Devices

ANN-RLY Board Layout and Connection to FACP

Figure 2.24 illustrates the ANN-RLY board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.

2.9.8 ANN-LC Lite-Connect Module

Specifications

Operating Voltage: 24 VDC

Max. Current: 150 mA

Operating Temperature: 32°F to 120°F (0°C to 49°C)

For indoor use in a dry location only

Installation

Ensure that all power (AC and DC) has been removed from the FACP before installing the
ANN-LC.

Mounting

The ANN-LC mounts inside the FACP cabinet. Slide the two tabs of the bracket into the backbox
protrusions on the lower right side. Secure with the included self-tapping screw. Refer to the
ANN-LC Product Installation Document
for more information.

Figure 2.24 ANN-RLY Connection to FACP

FACP

ANN-RLY

Primary ANN-BUS

+24 VDC

-24 VDC

ANN-BUS and power wiring are
supervised and power-limited

ANN-BUS (ID#)
Address DIP switch