Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 155

Advertising
background image

MS-9050 Series Manual — P/N 52413:G 4/14/2014

155

Calculating the System Current Draw

Power Supply Calculations

Table 7.3 contains columns for calculating current draws. For each column, calculate the current
and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation
Column 2 and Calculation Column 3 to Table 7.4 on page 156.

Calculation Column 1

Primary, Non-Fire Alarm Current

(amps)

Calculation Column 2

Primary, Fire Alarm Current

(amps)

Calculation Column 3

Secondary, Non-Fire Alarm Current

(amps)

Device Type

Qty

X [current draw] =

Total

Qty

X [current draw] =

Total

Qty

X [current draw] =

Total

Main Circuit Board

1

X[0.120]=

0.120

1

X[0.200]=

0.200

1

X[0.120]=

0.120

4XTMF

[ ]

X[0.005]=

[ ]

X[0.011]

1

=

[ ]

X[0.005]=

ANN-SEC Card

1 max

X[0.003]=

1 max

X[0.003]=

1 max

X[0.003]=

4-wire Detector Heads

[ ]

X[ ]

2

=

[ ]

X[ ]=

[ ]

X[ ]=

Power Supervision

Relays

3

[ ]

X[0.025]=

[ ]

X[0.025]=

[ ]

X[0.025]=

CP350 & CP355

[ ]

X[0.00030]=

maximum alarm draw

for all devices

0.400

[ ]

X[0.00030]=

SD350 & SD355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

SD350T & SD355T

[ ]

X[0.00030]=

[ ]

X[0.00030]=

AD350 & AD355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H350 & H355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H350R & H355R

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H355HT

[ ]

X[0.00030]=

[ ]

X[0.00030]=

D355PL

[ ]

X[0.00030]=

[ ]

X[0.00030]=

B200SR

4

[ ]

X[0.0005]=

[ ]

X[0.001]=

B224RB Relay Base

[ ]

X[0.00050]=

[ ]

X[0.00050]=

B224BI Isolator Base

[ ]

X[0.00045]=

[ ]

X[0.00045]=

MMF-300

[ ]

X[0.00050]=

[ ]

X[0.00040]=

MMF-300-10

[ ]

X[0.00350]=

[ ]

X[0.00350]=

MDF-300

[ ]

X[0.00075]=

[ ]

X[0.00075]=

MMF-301

[ ]

X[0.000375]=

[ ]

X[0.000375]=

MMF-302

[ ]

X[0.00027]=

[ ]

X[0.00027]=

MMF-302-6

[ ]

X[0.00200]=

[ ]

X[0.00200]=

BG-12LX

[ ]

X[0.00023]=

[ ]

X[0.00023]=

CMF-300

[ ]

X[0.00039]=

[ ]

X[0.00039]=

CMF-300-6

[ ]

X[0.00225]=

[ ]

X[0.00225]=

CRF-300

[ ]

X[0.00027]=

[ ]

X[0.00027]=

CRF-300-6

[ ]

X[0.00145]=

[ ]

X[0.00145]=

I300

[ ]

X[0.00040]=

[ ]

X[0.00040]=

ANN-80(C)

[ ]

X[0.0370]=

[ ]

X[0.0400]=

[ ]

X[0.0150]=

ANN-I/O

[ ]

X[0.0350]=

[ ]

X[0.2000]=

[ ]

X[0.0350]=

ANN-RLY

[ ]

X[0.0150]=

[ ]

X[0.0750]=

[ ]

X[0.0150]=

ANN-(R)LED

[ ]

X[0.0280]=

[ ]

X[0.0680]=

[ ]

X[0.0280]=

ANN-S/PG

[ ]

X[0.0450]=

[ ]

X[0.0450]=

[ ]

X[0.0450]=

ANN-LC

[ ]

X[0.150]=

[ ]

X[0.150]=

[ ]

X[0.150]=

NAC #1

[ ]

X[ ]=

NAC #2

[ ]

X[ ]=

Sum each column

5

for totals

Primary Non-Alarm =

Primary Alarm =

Secondary Non-Alarm =

Table 7.3 System Current Draw Calculations

1 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another

0.005 amps.

2 Refer to the Device Compatibility Document for standby current.
3 Must use compatible listed Power Supervision Relay.
4 Maximum alarm current for each sounder base is 0.035 amps which must be supplied by aux. 24VDC source.
5 Total current draw listed above cannot exceed 2.7 amps.