MS-9050 Series Manual — P/N 52413:G 4/14/2014

119

Maintenance Programming Level

Programming

3.6.12 Program Check

The Program Check feature allows the programmer to view the zones which have been pro-
grammed to the Notification Appliance Circuits on the control panel but have not been pro-
grammed to Initiating Devices as well as other circuits with no input or output correlations.
Pressing 3 while viewing Programming Screen #4 will cause the following screen to be displayed:

Pressing 1 while viewing the Program Check screen will display an NAC screen similar to the fol-
lowing.

The example above indicates that NAC 1 has been programmed to Zones 05, 10, 12, 15, and 17 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for NAC 1 and NAC 2.

Pressing 2 while viewing the Program Check screen will display a screen similar to the following:

The Zone No Input screen allows the programmer to view the zones which have not been pro-
grammed to at least one input device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able module (control module in this example) with an address of 001 on loop 1 but have not been
programmed to any input devices. Use the up and down arrow keys to view all the zones without
input assignments.

Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be
displayed:

The Zone No Output feature allows the programmer to view the zones which have not been pro-
grammed to at least one output device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able detector with an address of 001 on loop 1 but have not been programmed to any output
devices. Use the up and down arrow keys to view all the zones without output assignments.

3.7 Maintenance Programming Level

To access Maintenance Programming mode, press the Enter key. The LCD will display the follow-
ing:

PROGRAMMING

1=PASSWORD CHANGE

2=CLEAR PROGRAM

3=PROGRAM CHECK

Programming Screen #4

PROGRAM CHECK

1=NACS NO INPUT

2=ZONES NO INPUT

3=ZONES NO OUTPUT

PROGRAMCHECK

1=NACS NO INPUT

2=ZONES NO INPUT

3=ZONES NO OUTPUT

Program Check Screen

NACS NO INPUT

NAC 1

05 10 12 15 17

ZONES NO INPUT

05 07 09 10 11 1M001

ZONES NO OUTPUT

05 07 09 10 11 1D001

1=READ STATUS

2=PROGRAMMING

3=MANUAL DIAL MODE

4=REMOTE DOWNLOAD