MS-9050 Series Manual — P/N 52413:G 4/14/2014

Operating Instructions

Read Status

W - Walktestable for control and monitor modules (W = Yes, * = No)

Pressing the down arrow key, while viewing the screen shown above, will allow the operator to
view additional programming information about the selected device, such as:

Enable/Disable Status

Device Type

Alarm Verification On/Off (for detectors)

Walktest Yes/No

PAS (Positive Alarm Sequence) Yes/No (for detectors only)

Pre-Signal Yes/No (for detectors and monitor modules)

Zone Assignments (five maximum)

Adjective/Noun descriptor

Silenceable Yes/No (for control modules)

4.22.2 Zones

Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:

From the preceding screens, the control panel operator can view:

Zones Installed - all software zones programmed into the system (20 maximum)

Zones Enabled - all software zones that are enabled

Zones Disabled - all software zones that have been disabled

Special Purpose - on or off programming for Special Purpose Zones 17 reserved for PAS, 18
reserved for Pre-signal and 19 reserved for Two Stage Operation

Zone Type - the Type assigned to each installed zone (default is Alarm)

4.22.3 Power

Pressing 3 while viewing Read Status Screen #1 will cause the following screens to be displayed:

A real-time display of the control panel voltages can be used to determine if a problem exists in the
system.

The following table lists the circuit being measured, possible conditions and their respective volt-
age ranges:

READ STATUS

1=SYSTEM POINT

2=ZONES

3=POWER

Read Status Screen #1

ZONES

1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zones Screen #1

ZONES

1=SPECIAL PURPOSE

2=ZONE TYPE

3=FUTURE USE

Zones Screen #2

Circuit

Condition

Voltage Range

Battery

Normal Battery (nominal)

27.05 to 28.15 VDC

Low Battery

17.7 to 20.4 VDC

No Battery

0 to 17.6 VDC

ANN-BUS Power

Normal

21.25 to 27.50 VDC

Charger

Normal

21.87 to 29.84 VDC

System Power

Nominal

27.60 VDC

POWER

BATTERY 27.21V

ANN-BUS PWR 27.75V

CHARGER 27.75V

Power Screen #1

POWER

SYSTEM PWR 27.60V

Power Screen #2