Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 113

Advertising
background image

MS-9050 Series Manual — P/N 52413:G 4/14/2014

113

Master Programming Level

Programming

4+2 Standard, 4+2 Express, 3 + 1, 4 + 1, and 4+2 Expanded Formats

The information shown in Table 3.4 is automatically programmed for the Central Station phone
number Event Codes when any of these Formats are selected. Enter 00 for an Event Code
Setting to disable the report.

Event Description

Event Code Settings

Active

Restoral

PULL STATION

11

E1

MON-USER-DEF-1

11

E1

WATERFLOW

11

E1

MON-USER-DEF-2

11

E1

SMOKE (PHOTO)

11

E1

DET-USER-DEF-1

11

E1

SMOKE (ION)

11

E1

DET-USER-DEF-2

11

E1

HEAT DETECT

11

E1

DET-USER-DEF-3

11

E1

SMOKE DUCT-P

11

E1

DET-USER-DEF-4

11

E1

PHOTO W/HEAT

11

E1

DET-USER-DEF-5

11

E1

DUCT SUPERVISORY

81

E1

DET-USER-DEF-6

81

E1

PHOTO SUPERV

81

E1

DET-USER-DEF-7

81

E1

MONITOR

11

E1

MON-USER-DEF-3

11

E1

SMOKE CONVEN

11

E1

MON-USER-DEF-5

11

E1

HEAT CONVEN

11

E1

MON-USER-DEF-6

11

E1

MEDIC ALERT

00

00

MON-USER-DEF-7

00

00

HAZARD ALERT

00

00

MON-USER-DEF-8

00

00

TORNADO ALRT

00

00

MON-USER-DEF-9

00

00

TAMPER

81

E1

MON-USER-DEF-11

81

E1

MON SUPERVISORY

81

E1

MON-USER-DEF-12

81

E1

MON SUPERV AUTO

81

E1

MON-USER-DEF-13

81

E1

HVAC OVRRIDE

81

E1

POWER MON

81

E1

MON-USER-DEF-14

81

E1

TROUBLE MON

POINT_FAULT code will always be transmitted

MON-USER-DEF-15

POINT_FAULT code will always be transmitted

PROCESS MON

00

00

MON-USER-DEF-16

00

00

PROCMON AR

00

00

Table 3.4 Event Codes