4 circuits, Circuits – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 16

Advertising
background image

16

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Product Description

Circuits

AC Power (green)

Fire Alarm (red)

Supervisory (yellow)

Trouble (yellow)

Alarm Silenced signals (yellow)

Key Panel

Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.

Function keys:

Acknowledge/Step

Alarm Silenced

Drill (Manual Evacuate)

Reset (lamp test)

Service/program keys:

Keys labeled 1 to 9

* key

# key

0 (recall) key

1st Event key

Clear key

Escape key

Mode key

Four cursor keys (up, down, left and right)

Enter key

Local Piezo Sounder

A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi-
tions.

1.4 Circuits

SLC Communication Loop

One SLC loop is provided on the FACP main circuit board. The SLC loop, configurable for NFPA
Style 4, 6 or 7, provides communication to addressable detectors, monitor (initiating device) and
control (output device) modules. Refer to the SLC Wiring manual for information on wiring
devices.

Output Circuits

The following output circuits are available on the FACP:

Charger - 24 VDC Battery Charger (up to 18 AH batteries)

NAC (Notification Appliance Circuits) - Two NACs configurable for Style Y (Class B) or
Style Z (Class A), are provided with various programmable features.

Figure 1.2 Membrane/Display Panel

9050udkypd.cdr