3 controls and indicators, Controls and indicators – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 15

Advertising
background image

MS-9050 Series Manual — P/N 52413:G 4/14/2014

15

Controls and Indicators

Product Description

Special Application Primary ANN-BUS Power - TB3

Nominal Operating Voltage: 24 VDC
Maximum Current (Terminals 1 & 2): 500 mA
Power-limited, supervised

Special Application Secondary ANN-BUS Power - ANN-SEC - TB1

Nominal Operating Voltage: 24 VDC
Maximum Current (Terminals 1 & 2): 500 mA
Power-limited, supervised

The following figure illustrates the maximum current that is possible for each major panel output
circuit and the total current available from the FACP.

1.3 Controls and Indicators

LCD Display

The FACP uses an 80-character (4 lines X 20 characters) high
viewing angle LCD display. The display includes a long life
LED backlight that remains illuminated. If AC power is lost
and the system is not in alarm, the LED backlight will turn off
to conserve batteries.

LED Indicators

LED indicators are provided to annunciate the following conditions:

TB3

TB1

TB1

TB1

5

5

6

6

7

7

8

8

NAC #1

NAC #2

2.5 amps max

per circuit

2.5 amps max

per circuit

Alarm

2.5 amps max

per panel

Primary

ANN-BUS

Standby

1.0 amp max

per panel

0.5 amp max

per circuit

ANN-SEC

Option Card

0.5 amp max

per circuit

Figure 1.1 Current Availability

po

we

rd

is90

50

.wmf

Refer to the battery calculations section for additional information.

Nonresettable/

Resettable Power

#1

#2

1.0 amp max

per circuit

1.0 amp max

per circuit

OR

SYSTEM ALL NORMAL

10:00A 092105