82

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Master Programming Level

Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.

NACs: This feature allows the programmer to configure the control panel Notification
Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable,
autosilence, coding, silence inhibit, zone assignment and enable/disable.

Relays: This option allows programming of two onboard relays for activation by various
control panel events, such as alarm, trouble, supervisory, etc.

Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to “Canadian Option” on page 91).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.

Waterflow Silenceable: This option provides the ability to silence any output circuit activated
by a monitor module programmed as a waterflow type.

Lite-Connect: This options allows the programmer to enable the ANN-LC module and
configure the Lite-Connect circuit.

Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:

Trouble Reminder

The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to “System Setup” on page 81, for a
detailed description of this feature. Pressing 1 while viewing System Setup Screen #1 will cause
the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1 key will
cause the display to toggle between Trouble Rem On and Trouble Rem Off.

Banner

The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause
the following to be displayed:

Pressing 1 while viewing the Banner Screen will select the factory default banner setting and dis-
play the following screen:

The Factory Banner has now been selected and is stored in nonvolatile memory. Pressing the ESC
key will return the display to the Banner Screen.

PROGRAMMING

1=LOOP SETUP

2=SYSTEM SETUP

3=VERIFY LOOP

Programming Screen #2

SYSTEM SETUP

1=TROUBLE REM OFF

2=BANNER

3=TIME-DATE

System Setup Screen #1

SYSTEM SETUP

1=TIMERS

2=NAC

3=RELAYS

System Setup Screen #2

SYSTEM SETUP

1=CANADIAN OPT. OFF

2=WATERFLOW SIL. NO

3=LITE-CONNECT

System Setup Screen #3

BANNER

1=FACTORY

2=USER DEFINED

Banner Screen

BANNER

1=FACTORY

2=USER DEFINED

Banner Screen

FACTORY BANNER

Factory Banner Screen