117

Master Programming Level

Programming

Report Style

Pressing 3 while viewing Central Station Screen #2 will cause the Report Style display to toggle
between Point and Zone. Setting the Report Style to Point will program the DACT to report indi-
vidual point status to the Central Station. The control panel is capable of monitoring a total of 50
addressable devices. Setting the Report Style to Zone will program the DACT to report zone status
to the Central Station. The control panel is capable of monitoring a total of 20 individual zones.

Manual Dial Mode

Pressing 3 while viewing On Board DACT Screen #2 will cause the following screen to be dis-
played:

Note that Manual Dial Mode cannot be entered while the panel is communicating with the Central
Station.
Pressing 1 for Primary Phone or 2 for Secondary Phone will display the following screen:

Pressing 1 for Go Off Hook will cause the DACT to access the selected phone line (similar to tak-
ing the phone handset off the cradle). The selected phone line’s red Active LED will turn on.

Pressing 2 for Dial Digit(s) will display a screen which allows the user to key in the phone number
to be dialed. The first digit is keyed in and then the right arrow key is pressed to move the cursor to
the next position. The next digit is keyed in and the process is repeated until all digits have been
entered. Pressing the Enter key will cause the number just entered to be dialed.

Pressing 3 for Go On Hook will cause the DACT to hang-up, deselecting the previously selected
phone line. The phone line’s red Active LED will turn off.

Phone Line Supervision

Pressing 1 while viewing On Board DACT Screen #3 will cause the following screen to be dis-
played:

The Phone Line 2 option allows the programmer to select whether the second phone line is super-
vised. Pressing 1 while viewing the On Board DACT Screen #3 causes the display to toggle
between Yes and No. The factory default setting is Yes.

CENTRAL STATION

1=PRIMARY

2=SECONDARY

3=REPORT STYLE POINT

Central Station Screen #2

NOTES:
1. Detector/Module Address 01 will be reported to the Central Station as Point 01,
2. Detector/Module Address 02 as Point 02, with reports continuing in a similar fashion up to
Detector/Module Address 50 which will be reported as Point 50.

ON BOARD DACT

1=SERVICE TERMINAL

2=CENTRAL STATION

3=MANUAL DIAL MODE

On Board DACT Screen #2

MANUAL DIAL MODE

1=PRIMARY PHONE

2=SECONDARY PHONE

MANUAL DIAL MODE

1=GO OFF HOOK

2=DIAL DIGIT(S)

3=GO ON HOOK

NOTE: It is not necessary to go off-hook prior to dialing. Pressing the Enter key in Dial Digit
mode will cause the panel to automatically go off-hook prior to dialing.

ON BOARD DACT

1=SUPERV PHONE LINE

On Board DACT Screen #3

SUPERVISE PHONE LINE

1=PHONE LINE 2 YES