MBT-1 Municipal Box Trip - Silenceable

NFPA Standard-Specific Requirements

C.2 MBT-1 Municipal Box Trip - Silenceable

The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the
FACP and a Local Energy Municipal Box. The use of an addressable control module programmed
for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the
panel or box.

MS-9050UD

CMF-300 Control

Module

24 VDC,

Nonresettable

+ -

SLC Loop

B+ -B

Shield

red

black

MBT-1

brown wire

white wire

EOLR-1 Power
Supervision Relay

Alarm polarity shown!

_

+

-

To next device

+

on SLC Loop

Braided-shield/Drain Wire

The addressable

Control Module must

be programmed

as Silenceable and

General Alarm.

Gamewell Model M34-56

Local Energy Municipal Box

Note: 10

 maximum loop

resistance due to wiring from
power supply to Municipal Box.

Connect wires to two
red terminals on box.

(All contacts shown in energized position.)

Figure C.5 MBT-1 Silenceable

90

50

ud

_m

bt-

1.

w

mf