4 calculating the battery size, 1 nfpa battery requirements, 2 selecting and locating batteries – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 156: Calculating the battery size

Advertising
background image

156

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Power Supply Calculations

Calculating the Battery Size

7.4 Calculating the Battery Size

Use Table 7.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load
determines the battery size (in AH), required to support the control panel under the loss of AC
power. Complete Table 7.4 as follows:

1.

Enter the totals from Table 7.3 on page 155, Calculation Columns 2 and 3 where shown.

2.

Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below).

3.

Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere
hours.

4.

Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH).

5.

Write the ampere hour requirements on the Protected Premises label located inside the cabinet
door.

7.4.1 NFPA Battery Requirements

NFPA 72 Local and Proprietary Fire Alarm Systems require 24 hours of standby power
followed by 5 minutes in alarm.

NFPA 72 Central, Auxiliary and Remote Station Fire Alarm Systems require 60 hours of
standby followed by 5 minutes in alarm. Batteries installed in a system powered by a
generator need to provide at least 4 hours of standby power.

7.4.2 Selecting and Locating Batteries

Select batteries that meet or exceed the total ampere hours calculated in Table 7.4. The control
panel can charge batteries in the 7 AH to 18 AH range. The control panel cabinet is capable of
housing batteries up to 18 AH. Batteries larger than 18 AH require a UL listed external battery
charger and cabinet such as the BB-26, BB-55F, or other UL-listed external battery cabinet.

Secondary Standby Load
(total from Table 7.3 Calculation Column 3)
[ ]

Required Standby Time
(24 hours)
X [ ]

= AH

Primary Alarm Load
(total from Table 7.3 Calculation Column 2)

[ ]

Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
X[ ]

= AH

Sum of Standby and Alarm Ampere Hours

= AH

Multiply by the Derating Factor

X 1.2

Battery Size, Total Ampere Hours Required

= AH

Table 7.4 Total Secondary Power Requirements at 24 VDC

Advertising
This manual is related to the following products: