MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Maintenance Programming Level

3.7.6 Zone Setup

Pressing 3 while viewing Maintenance Screen #2 will display the following screen:

Pressing 1 while viewing Zone Setup screen will display the following screen:

A flashing cursor appears to the right of the Z. To enable a zone, enter the two digit zone number
(00 - 19). After the second digit is entered, the zone will be enabled and the cursor will return to the
original position. The next zone to be enabled can then be entered. Press Esc (Escape) to return to
the previous screen.

Pressing 2 while viewing Zone Setup screen will display the following screen:

A flashing cursor appears to the right of the Z. To disable a zone, enter the two digit zone number
(00 - 19). After the second digit is entered, the zone will be disabled and the cursor will return to
the original position. The next zone to be disabled can then be entered. Press Esc (Escape) to
return to the previous screen.

Pressing 3 while viewing Zone Setup screen will display the following screen:

Zones 17, 18, and 19 can be programmed for normal zone operation or for special purpose applica-
tions. In the above illustration, the three zones are shown Off, which means they can be pro-
grammed to function in the same manner as all other zones, by assigning them to input and output
devices in the Programming Zone Assignment Screen.

Pressing 1 will cause the display to change to PAS 17 On. Each press of the 1 key will cause the
display to toggle between PAS 17 On and PAS 17 Off. When Zone 17 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 17 to activate. By
assigning Zone 17 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control
panel. Do not assign Zone 17 to a Notification Appliance Circuit when using this zone to indicate a
PAS condition.

Pressing 2 will cause the display to change to Pre-signal 18 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 18 On and Pre-signal 18 Off. When Zone 18 is pro-
grammed On, a Pre-signal activation of any device will cause Zone 18 to activate. By assigning
Zone 18 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a Pre-signal condition in the control panel. Do
not assign Zone 18 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal
condition.

Pressing 3 will cause the display to change to Two Stage 19 On. Each press of the 3 key will cause
the display to toggle between Two Stage 19 On and Two Stage 19 Off. Refer to “Two Stage Opera-
tion” on page 88
for a description of this feature.

PROGRAMMING

1=WALKTEST

2=SYSTEM

3=ZONE SETUP

Maintenance Screen #2

ZONE SETUP

1=ENABLE

2=DISABLE

3=ZONE 17 18 19

Zone Setup Screen

ZONE TO ENABLE

Z

Enable Screen

ZONE TO DISABLE

Z

Disable Screen

SPEC PURPOSE ZONE

1=PAS 17 OFF

2=PRE-SIGNAL 18 OFF

3=TWO STAGE 19 OFF

Disable Screen