137

Read Status

Operating Instructions

Read Status Entry

When the operator presses the control panel Enter key, the LCD will display the following:

Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Sta-
tus mode which allows the user to view and print the programmed features and status of the control
panel.

The following screens will be displayed:

4.22.1 System Point

Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed:

The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for
Module. If 1 is pressed, the display will change to the following screen:

Entering the three digit detector address will cause the control panel to display the current status of
the selected device. For example, if a detector with address 001 on the SLC loop is entered, a dis-
play similar to the following will appear:

The information in the preceding display includes:

NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)

SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be
ION for ionization smoke detector)

NORTH CLASSROOM - the Adjective/Noun label for this device

Z005 - the first of five possible assigned software zones

1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001

V - Alarm Verification Enabled (V = Yes, * = No)

S - Silenceable for control modules (S = Yes, * = No)

1=READ STATUS MODE

2=PROGRAMMING MODE

3=MANUAL DIAL MODE

4=REMOTE DOWNLOAD

READ STATUS

1=SYSTEM POINT

2=ZONES

3=POWER

READ STATUS

1=TROUBLE REMINDER

2=TIMERS

3=NACS

Read Status Screen #1

Read Status Screen #3

READ STATUS

1=RELAYS

2=PROGRAM CHECK

3=HISTORY

Read Status Screen #5

READ STATUS

1=ANN-BUS

2=PHONE LINE

3=CENTRAL STATION

Read Status Screen #2

READ STATUS

1=SERVICE TERMINAL

2=PRINT

3=TIME-DATE

Read Status Screen #4

READ STATUS

1=SYSTEM POINT

2=ZONES

3=POWER

Read Status Screen #1

READ SYSTEM POINT

SELECT TYPE

1=DETECTOR

2=MODULE

READ SYSTEM POINT

ENTER DETECTOR#


NORMAL SMOKE(PHOTO)

NORTH CLASSROOM

Z005

V 1D001