1 transmittal priorities, Transmittal priorities – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 148

Advertising
background image

148

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Central Station Communications

Transmittal Priorities

5.1 Transmittal Priorities

The integral communicator transmits highest priority events first. Events, in terms of priority, are
listed below in descending order:

1.

Alarms (highest priority level)

Pull stations

Waterflow

Smoke detector

Other alarm types

2.

Supervisory Zone

3.

System Troubles

Zone disabled

Fire drill

AC fail (after delay)

Zonal faults

Earth fault

Low battery

Telephone line fault

Notification Appliance Circuits fault

Communication trouble

Annunciator trouble

System off normal

4.

Restoral Reports

Zone alarm

Supervisory

Zone(s) enabled

Fire drill

AC

Zone fault

Earth

Battery

Telephone line

Notification Appliance Circuits

Communication

Annunciator trouble

System off normal

5.

24 Hour Test (lowest priority)

Red LEDs are provided on the circuit board to identify which telephone line is activated. Also, a
green LED labeled Kissoff will turn on whenever the control panel has successfully transmitted
reports to the Central Station. The Kissoff LED may turn on several times during communications
with a Central Station.