MS-9050 Series Manual — P/N 52413:G 4/14/2014

75

Master Programming Level

Programming

Silenceable

The Silenceable selection allows the programmer to select whether output devices connected to the
control module can be silenced, either by pressing the Alarm Silence key or by enabling Autosi-
lence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable feature
causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the display to
toggle between Silenceable Yes and Silenceable No.

Note that nonsilenceable outputs will not be activated for Fire Drill.

Walktest

The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
Walktest Yes and Walktest No. Refer to“Walktest” on page 136 for additional information.

Zone Assignment

A maximum of five zones can be programmed to each addressable control module. Pressing 2
while viewing Edit Control Screen #3 displays the following screen:

Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zones Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Control Screen #3.

Adjective/Noun

The Adjective/Noun selection allows the programmer to enter specific descriptors about the control
module currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause
the following screen to be displayed:

EDIT CONTROL

1=ENABLED

2=TYPE

3=SILENCEABLE

Edit Control Screen #2

EDIT CONTROL

1=WALKTEST

2=ZONE ASSIGNMENT

00 QQ QQ QQ QQ

Edit Control Screen #3

ZONE ASSIGNMENT

Z00 ZQQ ZQQ ZQQ ZQQ

Zone Assignment Screen

EDIT CONTROL

1=ADJECTIVE/NOUN

2=DESCRIPTION

Edit Control Screen #4

1=STANDARD ADJECTIVE

2=STANDARD NOUN

3=CUSTOM ADJECTIVE

4=CUSTOM NOUN

Adjective/Noun Screen