4.22.8 Program Check

Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be
displayed:

Pressing 1 while viewing the Program Check screen will display a screen which will indicate if any
input zones have not been programmed to one of the Notification Appliance Circuits. Use the up
and down arrow keys to view all NACs.

Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any
output zones have not been programmed to at least one input zone. Use the up and down arrow
keys to view all zones.

Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any
input zones have not been programmed to at least one output zone. Use the up and down arrow
keys to view all zones.

4.22.9 History

Pressing 3 while viewing Read Status Screen #3 will display the following screen:

The operator can view all events which have been stored in the history file, only alarms or other
events, such as troubles or supervisories, by pressing the corresponding number key.

4.22.10 ANN-BUS

Pressing 1 while viewing Read Status Screen #4 will display the following screens:

Pressing 2 for Modules Installed, while viewing ANN-BUS Screen #1 will display screens with
ANN-BUS Addresses 1 through 8. Selecting an address will display information about the device
which has been assigned that address.

Pressing 3 for ANN-S/PG Options, while viewing ANN-BUS Screen #1 will display screens detail-
ing the setting for the ANN-SPG printer installed. This information includes:

Port Parallel/Serial

Printer Supervision Yes/No

Off Line Timer setting

Baud Rate

Data Bits

Parity

Stop Bits

Pressing 1 for ANN-80 Options, while viewing ANN-BUS Screen #2 will display screens detailing
the settings for this device. The information includes:

Piezo Enable/Disable

PROGRAM CHECK

1=NACS NO INPUT

2=ZONES NO INPUT

3=ZONES NO OUTPUT

HISTORY

1=VIEW ALL

2=VIEW ALARMS

3=VIEW OTHER EVENTS

ANN-BUS

ENABLED

2=MODULES INSTALLED

3=ANN-S/PG OPTIONS

ANN-BUS Screen #1

ANN-BUS

1=ANN-80 OPTIONS

2=ANN-SECONDARY

ANN-BUS Screen #2

Advertising
This manual is related to the following products: