UL Power-limited Wiring Requirements

Installation

2.6 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-lim-
ited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through dif-
ferent knockouts and/or conduits. If installing an optional ANN-LC, ensure that the ground for the
AC mains is installed first, closest to the backbox. A typical wiring diagram for the FACP is shown
below.

TB1

J1

Figure 2.7 Typical UL Power-limited Wiring Requirements

Power-limited Circuits (Class 2)

Power-limited
Circuits (Class 2)

Nonpower-limited Circuits (Class 1)

Nonpower-
limited, (Class 1)
supervised
Telephone
Circuit

AC Power

Hot

Neutral

Ground

9

0

50

ud

ul

pwr

3

.w

mf

To Batteries

(nonpower-limited,

Class 1, supervised)

maintain minimum 0.25” between power-
limited and nonpower-limited circuits wiring

Ground Stud

Transformer

Wires

(nonpower-

limited,

supervised)

4XTMF

ANN-SEC

Power-limited
Circuits
(Class 2)

dashed lines
represent wiring
behind PCB

Power-limited

Circuits

(Class 2)

Nonpower-
limited,
supervised
Fiber Circuit