Read Status

Operating Instructions

Allows a smoke detector to retain its original ability to detect actual smoke and resist false
alarms, even as dirt and dust accumulate

Reduces maintenance requirements by allowing the control panel to automatically perform the
periodic sensitivity measurements required by NFPA Standard 72

The FACP software also provides filters to remove transient noise signals, usually caused by elec-
trical interference.

Maintenance Alert

The software determines when the drift compensation for a detector reaches an unacceptable level
that can compromise detector performance. When a detector reaches an unacceptable level, the
control panel indicates a maintenance alert. Table 4.1 summarizes the three levels of maintenance
alert:

Figure 4.1 illustrates a graphic representation of the maintenance levels:

Pressing 2 while viewing Print Screen #2 allows the user to print the DACT summary which will
detail all of the onboard DACT settings. Refer to “Onboard DACT” on page 106 for additional
information on the display.

Pressing 3 while viewing Print Screen #2 exits the user from the print menu.

4.22.15 Time-Date

The operator can view the daylight savings time and the month and week when daylight savings
time will begin and end. Pressing 3 while viewing Read Status Screen #5 will display the following
screens:

Maintenance Level

FACP Status Displays Indicates

Low Chamber Value

INVREP

A hardware problem in the detector

Maintenance Alert

DIRTY1

Dust accumulation that is near but below the allowed
limit. DIRTY 1 indicates the need for maintenance
before the performance of the detector is compromised

Maintenance Urgent

DIRTY2

Dust accumulation above the allowed limit.

Table 4.1 Maintenance Alert Levels

Figure 4.1 Diagram of Maintenance Levels

DIRTY

Acceptable

Range

Maintenance
Urgent

Maintenance
Alert

Low Chamber
Reading

LOW

VALUE

READ STATUS

1=SERVICE TERMINAL

2=PRINT

3=TIME-DATE

Read Status Screen #5

DAYLIGHT SAVINGS

ENABLED YES

START MONTH MAR

START WEEK WEEK 2

DAYLIGHT SAVINGS

END MONTH NOV

END WEEK WEEK 1