background image

MS-9050 Series Manual — P/N 52413:G 4/14/2014

139

Read Status

Operating Instructions

4.22.4 Trouble Reminder

Pressing 1 while viewing Read Status Screen #2 will display the following screen:

The screen indicates whether the Trouble Reminder feature is On or Off. The factory default set-
ting is Trouble Rem OFF.

4.22.5 Timers

Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be dis-
played:

These screens will indicate the delay time, in seconds, for each of the first three possible delay
options. The AC Loss Delay time is displayed in hours.

4.22.6 NAC

Pressing 3 while viewing Read Status Screen #2 will display the following screen:

The operator can press 1 to view the programmed options for NAC 1 or 2 to view the programmed
options for NAC 2. The resulting screens will display the following information:

Enable/Disable Status

Circuit Type (Bell, Strobe, etc.)

Silenceable/Nonsilenceable

Auto Silence Enable/Disable and time delay (in minutes)

Coding Selection (Temporal, Steady, etc.)

Zone Assignments

Silence Inhibit Enabled/Disabled

Synchronization Type (System Sensor, Wheelock, or Gentex)

4.22.7 Relays

Pressing 1 while viewing Read Status Screen #3 will display the following screen:

The operator can view the programmed option for each relay by pressing the corresponding number
key.

READ STATUS

1=TROUBLE REMINDER

2=TIMERS

3=NAC

Read Status Screen #2

TROUBLE REMINDER

TROUBLE REM ON

TIMERS

PAS DELAY 000

PRE SIGNAL 000

WATERFLOW 000

TIMERS

AC LOSS DELAY 2

NAC

1=NAC 1

2=NAC 2

READ STATUS

1=RELAYS

2=PROGRAM CHECK

3=HISTORY

Read Status Screen #3

RELAY

1=RELAY 1

2=RELAY 2

3=RELAY 3