Master Programming Level

Programming

Ademco Contact ID Format

The information shown in Table 3.5 is automatically programmed for the Central Station phone
number Event Codes when Ademco Contact ID Format is selected. Enter 000 for an Event Code
Setting to disable the report.

Event Description

Event Code Settings

4+2

Active

Zone

Point

Restoral

Active

PULL STATION

115

Zone

Point

E1

11

MON-USER-DEF-1

115

Zone

Point

E1

11

WATERFLOW

113

Zone

Point

E1

11

MON-USER-DEF-2

113

Zone

Point

E1

11

SMOKE (PHOTO)

111

Zone

Point

E1

11

DET-USER-DEF-1

111

Zone

Point

E1

11

SMOKE (ION)

111

Zone

Point

11

11

DET-USER-DEF-2

111

Zone

Point

11

11

HEAT DETECT

114

Zone

Point

11

11

DET-USER-DEF-3

114

Zone

Point

11

11

SMOKE DUCT-P

116

Zone

Point

11

11

DET-USER-DEF-4

116

Zone

Point

11

11

PHOTO W/HEAT

111

Zone

Point

11

11

DET-USER-DEF-5

111

Zone

Point

11

11

DUCT SUPERVISORY

200

Zone

Point

11

81

DET-USER-DEF-6

200

Zone

Point

11

11

PHOTO SUPERV

200

Zone

Point

11

81

DET-USER-DEF-7

200

Zone

Point

11

11

MONITOR

110

Zone

Point

11

11

MON-USER-DEF-3

110

Zone

Point

11

11

SMOKE CONVEN

111

Zone

Point

81

11

MON-USER-DEF-5

111

Zone

Point

11

11

HEAT CONVEN

114

Zone

Point

81

11

MON-USER-DEF-6

114

Zone

Point

11

11

MEDIC ALERT

100

Zone

Point

11

0

MON-USER-DEF-7

100

Zone

Point

11

0

HAZARD ALERT

150

Zone

Point

11

0

MON-USER-DEF-8

150

Zone

Point

11

0

TORNADO ALRT

150

Zone

Point

11

0

MON-USER-DEF-9

150

Zone

Point

11

0

TAMPER

144

Zone

Point

0

81

MON-USER-DEF-11

144

Zone

Point

0

81

MON SUPERVISORY

200

Zone

Point

0

81

MON-USER-DEF-12

200

Zone

Point

0

81

MON SUPERV AUTO

200

Zone

Point

0

81

MON-USER-DEF-13

200

Zone

Point

0

81

HVAC OVRRIDE

200

Zone

Point

81

81

POWER MON

330

Zone

Point

81

81

MON-USER-DEF-14

330

Zone

Point

81

81

TROUBLE MON

POINT_FAULT code will always be transmitted

81

MON-USER-DEF-15

POINT_FAULT code will always be transmitted

81

PROCESS MON

000

81

0

MON-USER-DEF-16

000

81

0

PROCMON AR

000

81

0

Table 3.5 Event Codes