MS-9050 Series Manual — P/N 52413:G 4/14/2014

Installation

ANN-BUS Devices

With an ANN-SEC Card

Connect the ANN-SEC as shown in Section 2.8.2. Connect TB1 on the ANN-SEC to TB1 on the
ANN-LC as shown below. Additional secondary ANN-BUS devices can be connected to TB2 on
the ANN-LC.

Programming

Following installation and wiring of the ANN-LC module to the FACP, the module must be added
to the system via FACP programming. Select the LCD option for system programming. Refer to the
programming section titled “Lite-Connect” on page 91 in this manual for detailed programming
information.

J13

TB

1

J1

ANN-SEC

B A+ -

+ - B A

to ANN-BUS
devices
downstream

MS-9050UD

ANN-LC

TB1

TB2

TB1

Figure 2.27 Wiring the ANN-LC to the MS-9050UD Via the ANN-SEC Card

90

50

secto

F

LL

C.

wm

f

power-

limited,

supervised

power-

limited,

supervised

Note: Figure 2.27 is just a
graphical representation for
terminal wiring purposes only.
Actual wiring from the ANN-SEC
to the ANN-LC should be run
behind the board, between the
board and chassis. Maintain at
least 0.25” (6.35 mm) spacing
between power-limited and
nonpower-limited circuit wiring.