Hazard/Tornado Condition Operation

Operating Instructions

The LCD displays a process monitor message along with the device name, type, address,
adjective/noun, associated zones, and time/date

Communicate the process monitor condition to the Central Station (if the default event code
has been changed from 000 to a reportable event code)

Relays programmed for process monitoring will be activated

The alarm relay is not activated

Fire Alarm NACs will not activate

SLC NACs (control modules) will activate

Timers are not started

Store event in history buffer

Activate appropriate LED on the ANN-LED annunciator (required for this application)

Each ANN-LED can support up to 10 zones.

Note that, like supervisories, process monitor signals latch (except when programmed for process
monitor autoresettable) and can be assigned to software zones.

4.8 Hazard/Tornado Condition Operation

Hazard/Tornado operation is intended for Manual activation.

Hazard/Tornado Condition operation will initiate the following events:

The piezo sounder pulses ¼ second On, ¼ second Off

The LCD displays a hazard message along with the device name, type, address,
adjective/noun, associated zones, and time/date

Communicate the hazard condition to the Central Station (if the default event code has been
changed from 000 to a reportable event code)

Relays programmed for hazard will be activated

The alarm relay is not activated

Fire Alarm NACs will not activate

SLC NACs (control modules) will activate

Timers are not started

Store event in history buffer

Activate appropriate LED on the ANN-LED annunciator (required for this application)

Each ANN-LED can support up to 10 zones.

Hazard conditions latch. They can be assigned to software zones.

4.9 Medical Alert Condition Operation

Medical alert operation is:

not intended for nurse call stations (applications) per UL1069.

not intended for signaling professional medical staff.

to be used for summoning security guards or other trained personnel within the facility

intended for Manual activation.

Medical Alert Condition operation will initiate the following events:

The piezo sounder ¼ second On, ¼ second Off

The LCD displays a medical alert message along with the device name, type, address,
adjective/noun, associated zones, and time/date

Communicate the medical alert condition to the Central Station (if the default event code has
been changed from 000 to a reportable event code)