MS-9050 Series Manual — P/N 52413:G 4/14/2014

87

Master Programming Level

Programming

Enabled

Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.

Type

The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1.
The following screen will be displayed. Press the down arrow key to view additional screens:

Select the NAC device type by pressing the number corresponding to the type in the appropriate
screen. When the selection is made, the display will return to NAC Screen #1.

The following table contains NAC type codes and their functions:

Silenceable

Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This
will prevent the selected main circuit board NAC from being silenced by pressing the Alarm
Silence key or by the Auto Silence feature. Each press of the 3 key will cause the display to toggle
between Silenceable Yes and Silenceable No.

Important: When a Notification Appliance Circuit with a mix of audible and visual devices is pro-
grammed for silenceable and the synchronization feature is selected, only the audible devices will
be turned off if the Silence key is pressed or if the Autosilence feature is enabled. The visual devices
(strobes, etc.) will continue to operate.

Auto Silence

The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following
screens will be displayed:

NAC Type Code

Special Function

Bell

None

Horn

None

Strobe

None

Synced Strobe

Synchronized to manufacturer

Strobe Sil Sync

Same as Synced Strobe but Silence turns off audible & visual devices

Door Holder

NAC normally active

1

1 Important: User should be aware that selecting Door Holder, Reset Power or

Non-Reset Power types for an NAC will immediately activate (turn on) the NAC
circuit and any devices connected to it, and therefore should not be used for
notification appliances.

Reset Power

NAC normally active

1

Non-Reset Power

NAC normally active

1

NAC #

1=ENABLED

2=TYPE

3=SILENCEABLE

NAC Screen #1

NAC TYPE

1=BELL

2=HORN

3=STROBE

Type Screen #1

NAC #

1=AUTO SILENCE

2=CODING

TEMPORAL

NAC Screen #2

AUTO SILENCE

1=NO

2=5 MINUTES

3=10 MINUTES

Auto Silence Screen #1

AUTO SILENCE

1=30 MINUTES

Auto Silence Screen #2

AUTO SILENCE

1=15 MINUTES

2=20 MINUTES

3=25 MINUTES

Auto Silence Screen #3

Advertising