MS-9050 Series Manual — P/N 52413:G 4/14/2014

29

Relays

Installation

2.4 Relays

The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble
relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).

Note that relay connections must be nonpower-limited. Refer to UL Power-limited wiring require-
ments.

AC Connection to

Transformer leads:

HOT

NEUTRAL

Battery Connection

to J1 on FACP

Ground Stud

90

50

ud

p

o

wr

.c

d

r

Figure 2.5 Relay Terminals

Relay contacts shown with power applied to panel

and no active troubles, alarms or supervisories

Note that the programmable relay
labeled as Relay 1 is factory default
programmed as Alarm and
programmable Relay 3 is factory default
programmed as Supervisory. The relay
labeled Relay 2 is fixed as a Trouble
relay and cannot be changed. It is a fail-
safe relay which will transfer on any
trouble or total power failure.