Section 6: Local/Remote Site Upload/Download

The control panel may be programmed or interrogated off-site via the public switched telephone
network. Any personal computer with Windows

®

XP or greater, with a 2400 baud compatible

modem and Fire-Lite Upload/Download software kit P/N PK-CD, may serve as a Service Terminal.
This allows download of the entire program or upload of the entire program, history file, walktest
data, current status, time and date.

The control panel may also communicate to a local PC at the job-site. The PC must be connected
to TB3 as shown on page 10, using cable P/N: PRT/PK-CABLE.

Important: Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to “Remote Download” on page 150
). Remote interrogation of panel pro-
gramming, history logs, detector status, etc., is possible without enabling the remote download
option.

CAUTION: To prevent the 'request for upload/download' message(s) from being reported to the
Central Station(s), make certain to disable all upload/download reports back to both Central Sta-
tions (refer to “Central Station” on page 107).

After the downloading process, the fire protection may be inactive for up to 2 minutes while the fire
panel re-initializes.

After successfully downloading a program, make certain to perform the following steps:

1.

Review all programmed entries and compare to intended program data

2.

Test all affected panel operations

3.

Immediately correct any problems found

6.1 Remote Download

NFPA 72 requirements state that a technician must be on-site and at the control panel whenever the
PS-Tools programming utility is used to download any information to the FACP. For this reason, a
new option has been added to the FACP which allows an individual at the FACP to enter a pass-
word and either enable the proprietary mode where downloading will be allowed at any time or
access a specific password protected screen where downloading will be allowed regardless of the
current proprietary setting. The Remote Download option can be selected from the main menu
screen as shown below:

Pressing 4 for Remote Download while viewing the main menu will cause the following screen to
be displayed:

The Remote Download password (default 00000) must be entered to access the Remote Download
feature. Note that the default password can be changed using the Password Change option (refer to
“Password Change” on page 118). Entering the correct password will cause the following screen to
be displayed:

1=READ STATUS MODE

2=PROGRAMMING MODE

3=MANUAL DIAL MODE

4=REMOTE DOWNLOAD

REMOTE DOWNLOAD

ENTER PASSWORD


REMOTE DOWNLOAD

1=PROPRIETARY NO

2=ACCEPT DOWNLOAD