Zones available – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 80

Advertising
background image

80

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Master Programming Level

The Zones Installed screen will show the system zones (default and user programmed) and their
associated types. Note that an up and/or down arrow will appear in the upper right corner of the
display, indicating that additional screens of zone information exists. Press the up or down arrow
keys to view zones Z00 through Z19.

Zone types can be changed by pressing the keypad number key corresponding to the zone in each
Zones Installed Screen. Available zone types will be displayed in the resultant screens. For exam-
ple, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following
screens will be displayed:

To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.

IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow
silenceable zone type to the selected zone. Any signaling devices programmed to the same zone can
be silenced by pressing the Alarm Silence key or by using the auto-silence feature.

To program a waterflow circuit as nonsilenceable, refer to “System Setup” on page 81 and “Water-
flow Silenceable” on page 91.

Zones Available

Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:

The display will show all of the zones that are still available for programming.

ZONE TYPE PROG

1=MONITOR

2=SMOKE PHOTO

3=WATERFLOW

Zone Type Program Screen #1

ZONE TYPE PROG

1=MEDICAL

2=HAZARD

3=TAMPER

Zone Type Program Screen #5

ZONE TYPE PROG

1=NONE

Zone Type Program Screen #4

ZONE TYPE PROG

1=HEAT

2=PULL STATION

3=DUCT

Zone Type Program Screen #3

ZONE TYPE PROG

1=SUPERVISORY

2=PROC. MON

3=SMOKE ION

Zone Type Program Screen #2

NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will
only change how it is reported to the Central Station.

NOTE: If a tornado zone is required, choose Zone Type “Hazard”.

ZONE SETUP

1=ZONE TYPES

2=ZONES AVAILABLE

3=FUTURE

Zone Setup Screen #3

ZONES AVAILABLE

01 02 03 04 05 06 07

08 09 10 11 12 13 14

15 16 17 18 19