Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 68

Advertising
background image

68

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Master Programming Level

If the selected address has been added to programming and a module (such as a monitor module)
with the selected address is physically installed on the SLC and is communicating with the control
panel, the following screen will be displayed:

To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Monitor screens.

In the preceding example:

Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)

<ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device

ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the two digit zone number from 000 - 019)

1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module
and 012 = Module Address 012)

W or * - indicates whether or not the device is programmed for Walktest (W = programmed
for walktest, * = not programmed for walktest).

If the selected address corresponds to a control module, a screen displaying information about the
control module with the selected address will be displayed as shown in “Edit Module Screen for
Control Modules” on page 73.

If the selected address corresponds to a monitor module, a screen displaying information about the
module with the selected address will be displayed as illustrated in the following:

Enable/Disable Module

To Enable or Disable the monitor module, press the 1 key while viewing the Edit Module Screen
#2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled
No
is selected, the module will not be polled by the control panel, preventing the module from
reporting alarms and troubles to the panel. The control panel will indicate a system trouble condi-
tion if any devices are disabled.

Type Monitor

Using the PK-CD Upload/Download utility program, unique user-defined monitor types can be cre-
ated and loaded into the FACP for later use. The FACP response to the activation of a user-defined
type is the same as most previous standard types in the list, thus allowing a variety of user-defined

NORMAL MONITOR

<ADJ><NOUN>

ZNNN

W 1M012

NORMAL MONITOR

<ADJ><NOUN>

ZNNN

1M012

EDIT MONITOR 1M012

1=ENABLED YES

2=TYPE MONITOR

Edit Monitor Screen #2

EDIT MONITOR 1M012

1=PRE-SIGNAL NO

Edit Monitor Screen #3

EDIT MONITOR 1M012

1=WALKTEST YES

2=ZONE ASSIGNMENT

00 QQ QQ QQ QQ

Edit Monitor Screen #4

EDIT MONITOR 1M012

1=ADJECTIVE/NOUN

2=DESCRIPTION
QQQQQQQQQQQQQQQQQQQQ

Edit Monitor Screen #5

EDIT MONITOR

1=ENABLED

2=TYPE MONITOR

Edit Monitor Screen #2