MS-9050 Series Manual — P/N 52413:G 4/14/2014

Installation

ANN-BUS Devices

ANN-LED Board Layout and Connection to FACP

Figure 2.22 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.

2.9.7 ANN-RLY Relay Module

The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compat-
ible FACP.

Specifications

Operating Voltage: 24 VDC

Max. Current:

Alarm: 75 mA

Standby: 15 mA

Operating Temperature: 32

o

F to 120

o

F (0

o

C to 49

o

C)

For indoor use in a dry location only

Figure 2.22 ANN-LED Connection to FACP

ANN-LED

+24 VDC

-24 VDC

ANN-BUS and power wiring are
supervised and power-limited

MS-9050UD

Primary ANN-BUS

Ground wire from mounting screw to
FACP Earth Ground stud is required
for some Canadian applications.
(Refer to “ANN-LED Annunciator
Installation for Canadian
Applications” on page 181)
.

ANN-BUS (ID#)