12

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Section 1: Product Description

The MS-9050UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm
Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent
addressable control panel has an extensive list of powerful features. The combination of Fire-Lite’s
newer series devices and legacy 300 Series devices, along with the MS-9050UD FACP, offer the
latest in fire protection technology. The power supply and all electronics are contained on a single
circuit board housed in a metal cabinet, providing a complete fire control system for most applica-
tions. Available accessories include local and remote upload/download software, remote annuncia-
tors and reverse polarity/city box transmitter.

The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via
the public switched telephone network. It also allows remote programming or interrogation of the
control panel using the PS-Tools Upload/Download utility via the public switched telephone net-
work. Any personal computer with Windows

®

XP or newer, and compatible modem with a speed

of 2400 baud or faster and Upload/Download software kit PK-CD, containing PS-Tools, may serve
as a Service Terminal. This allows download of the entire program or upload of the entire program,
history file, walktest data and current status.

The MS-9050UDC is a ULC-approved Canadian version of the FACP which offers the same fea-
tures as the MS-9050UD, but is supplied standard with a dress panel and one built-in ANN-LED
annunciator. Refer to“Canadian Option” on page 91 for a full description.

The MS-9050UDE offers the same features as the MS-9050UD but allows connection to 220/240
VAC power.

Inventory

When the MS-9050UD shipment is received, check to make certain that all parts have been
included in the shipment. The MS-9050UD shipment should consist of one of each of the follow-
ing:

main circuit board with display

chassis with transformer

backbox with door

plastic bag containing screws, cables, key, etc.

manual

1.1 Features and Options

Built-in DACT (Digital Alarm Communicator/Transmitter) with remote upload/download

Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements

50 addressable device capacity (any combination of addressable detectors and addressable
control/relay/monitor modules totaling 50)

20 software zones

Two onboard NACs (Notification Appliance Circuits) which can be configured as Style Y
(Class B) or Style Z (Class A) circuits

2.5 amps total output power

Two programmable relays and one fixed trouble relay

Built-in Programmer

Telephone Line Active LEDs

NOTE: Unless otherwise specified, the terms FACP and MS-9050UD are used in this manual to
refer to all versions of the FACPs.