Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual

Page 62

Advertising
background image

62

MS-9050 Series Manual — P/N 52413:G 4/14/2014

Programming

Master Programming Level

Type

To select the type of detector being programmed, press the 2 key while viewing the Edit Detector
Screen #2. This will cause the control panel to display the following Detector Type Screen:

Pressing the down arrow key will display additional detector types as indicated in the following
table.

While viewing any Detector Type screen, select the type of detector being programmed by pressing
the corresponding keyboard number key. The display will return to Edit Detector Screen #2 and
indicate the selection next to the Type option.

Verification

Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and
not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2
so that the display reads Verification On. Each time the 3 key is pressed, the display will toggle
between Verification On and Verification Off. For a detailed description, refer to “Alarm Verifica-
tion (None or One Minute)” on page 135.

Walktest

The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable a device for the Walktest feature,
press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes. Each press
of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to “Walk-
test” on page 136.

Detector Type

Action When Activated

Smoke Photo

Fire Alarm

User-Defined-1

same as previous (Smoke Photo)

Smoke Ion

Fire Alarm

User-Defined-2

same as previous (Smoke Ion)

Heat Detect

Fire Alarm

User-Defined-3

same as previous (Heat Detect)

Smoke DuctP

Fire Alarm

User-Defined-4

same as previous (Smoke DuctP)

Photo w/Heat

Fire Alarm

User-Defined-5

same as previous (Photo w/Heat)

Duct Superv

Supervisory, latching

User-Defined-6

same as previous (Duct Superv)

Photo Superv

Supervisory, latching

User-Defined-7

same as previous (Photo Super)

future

not used

EDIT DETECTOR

1=ENABLED

2=TYPE

3=VERIFICATION

Edit Detector Screen #2

DETECTOR TYPE

1=SMOKE(PHOTO)

2=USER-DEFINED-1

3=SMOKE (ION)

Detector Type Screen #1

NOTE:

If a detector is selected to be a SUPERV DUCTP type, it will function like a

supervisory point not a fire alarm point. The supervisory LED and supervisory relay will
activate, not the fire alarm LED or alarm relay, if the detector senses smoke.

EDIT DETECTOR

1=WALKTEST

2=PAS

3=PRE-SIGNAL

Edit Detector Screen #3

Advertising
This manual is related to the following products: