93

Master Programming Level

Programming

A flashing cursor will appear in the lower left corner of the display. Enter the four-digit account
code for each central station. After the last digit is entered, the display will return to the Account
Code screen.

Node Mode Setup

Pressing 3 while viewing the Lite-Connect Setup Screen will allow the programmer to configure
the MS-9050UD as a node on the Lite-Connect circuit.

Pressing 1 while viewing the Node Mode Setup Screen will allow the programmer to enable the
MS-9050UD as a node on the Lite-Connect circuit. Select Enabled Yes if an ANN-LC has been
installed and wired to the secondary ANN-BUS port. Each press of the 1 key will toggle the
display between Enabled No and Enabled Yes.

Pressing 2 while viewing the Node Mode Setup Screen will allow the programmer to enter the
address of the node on the Lite-Connect circuit.

A flashing cursor will appear in the lower left corner of the display. Enter the two-digit address
which can be a value between 02 and 17. Address 01 is reserved for the hub. After the second digit
is entered, the display will return to the Node Mode Setup screen.

3.6.6 Verify Loop

Pressing 3 while viewing Programming Screen #2, will select the Verify Loop option. During loop
verification, the FACP polls each device on the SLC to determine if the device is communicating
and whether or not it responds with the proper type identification. The following screen will be dis-
played while verification is in progress:

When Loop verification has been completed, the display will indicate that the system is OK or, if
problems have been detected, any device type programming errors. Use the up and down arrow
keys to view all detected errors.

3.6.7 History

The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 1 while viewing Programming Screen #3 will display the History options
as shown in the following display:

LITE-CONNECT

1=ENABLED YES

2=HUB MODE SETUP

3=NODE MODE SETUP

Lite-Connect Setup Screen

NODE MODE SETUP

1=ENABLED YES

2=ADDRESS ##

Node Mode Setup Screen

NODE ADDRESS

ENTER NODE ADDRESS

RANGE 02-17

Node Mode Setup Screen

PROGRAMMING

1=LOOP SETUP

2=SYSTEM SETUP

3=VERIFY LOOP

Programming Screen #2

VERIFYING LOOPS

PLEASE WAIT

Verification Progress Screen

PROGRAMMING

1=HISTORY

2=WALKTEST

3=OPTION MODULES

Programming Screen #3

HISTORY

1=VIEW EVENTS

2=ERASE HISTORY

History Screen