MS-9050 Series Manual — P/N 52413:G 4/14/2014

165

NFPA Standard-Specific Requirements

NFPA 72 Auxiliary Fire Alarm System

All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.

Notes:

1.

3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.

2.

Cut JP28 on the MS-9050UD main circuit board to supervise placement of 4XTMF module
and circuit.

3.

Remove JP2 on the MS-9050UD main circuit board to enable FACP Supervisory relay.

4.

Refer to “4XTMF Transmitter Module Installation” on page 33 for detailed information.

NFPA 72 Remote Station Protective Signaling System

Notes:

Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module

FIRE

Gamewell Model M34-56 Local
Energy Municipal Box

Polarities shown in alarm condition

+

Nonpower-limited

Municipal Box Circuit

+

-

-

4XTMF