ANN-80 Options Screen

Pressing 2 while viewing ANN-BUS screen #2 will display the following screen:

The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options Screen
#1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.

The Lock Enable option allows the programmer to select whether or not any installed ANN-80
annunciator must be unlocked by its key before any annunciator key presses will function. Pressing
2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Lock Enable
Yes
(annunciator must be unlocked for keys to function) and Lock Enable No (lock position is
ignored).

The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 annunciator will function normally or
always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display to
toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No
(Ack/Step button never functions).

The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the
Silence button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Sil
Btn Enable Yes
(Silence button functions normally) and Sil Btn Enable No (Silence button never
functions).

The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the
Reset button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Rst
Btn Enable Yes
(Reset button functions normally) and Rst Btn Enable No (Reset button never func-
tions).

The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the
Drill button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Drl
Btn Enable Yes
(Drill button functions normally) and Drl Btn Enable No (Drill button never func-
tions).

ANN-SECONDARY Options Screen

Pressing 3 while viewing ANN-BUS screen #2 will display the following screen:

The ANN-SECONDARY must be enabled if any modules are connected to the ANN-SEC option
card at J13. To enable the Secondary ANN-BUS, press 1 while viewing ANN-SECONDARY
screen so that the display reads ANN-SECONDARY Enabled Yes. Each press of the 1 key will
cause the display to toggle between ANN-SECONDARY Enabled Yes and ANN-SECONDARY
Enabled No
. The factory default setting is ANN-SECONDARY Enabled No.

ANN-80 OPTIONS

1=PIEZO ENABLE

2=LOCK ENABLE

3=ACK BTN ENABLE

ANN-80 Options Screen #1

ANN-80 OPTIONS

1=SIL BTN ENABLE

2=RST BTN ENABLE

3=DRL BTN ENABLE

ANN-80 Options Screen #2

ANN-SECONDARY

1=ENABLED NO