Programming

Master Programming Level

ANN-BUS

Pressing 1 while viewing the Option Modules screen will cause the control panel to display the fol-
lowing screens.

A printer module and LCD annunciator module can be programmed into the MS-9050UD system.
These devices communicate with the FACP over the ANN-BUS terminals on the control panel.

ANN-BUS Enabled

The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads ANN-
BUS Enabled Yes.
Each press of the 1 key will cause the display to toggle between ANN-BUS
Enabled Yes
and ANN-BUS Enabled No. The factory default setting is ANN-BUS Enabled No.

Modules Installed

If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN-
BUS addresses for the module(s). The following screen will be displayed.

Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1-8. To select one or more addresses for the installed module(s), press the number key
corresponding to the module address in each screen. The following screens will be displayed for
each address:

Pressing 1 for Type will display the following screens:

Press the number corresponding to the module type that is installed with the selected address.

ANN-BUS

1=ENABLED NO

2=MODULES INSTALLED

3=AUTO-CONFIGURE

ANN-BUS Screen #1

ANN-BUS

1=ANN-S/PG OPTIONS

2=ANN-80 OPTIONS

3=ANN-SECONDARY

ANN-BUS Screen #2

ANN-BUS MODULES

1=ADDR. 1 NONE

2=ADDR. 2 NONE

3=ADDR. 3 NONE
ANN-BUS Modules Screen #1

ANN-BUS MODULE

ANN-BUS ADDRESS #

1=TYPE NONE

ANN-BUS MODULE TYPE

1=NOT INSTALLED

2=ANN-80 MODULE

3=ANN-I/O MODULE

Module Type Screen #1

ANN-BUS MODULE TYPE

1=ANN-S/PG MODULE

2=ANN-LED MODULE

3=ANN-RLY MODULE

Module Type Screen #2

NOTE:

If the module type selected is the ANN-80 or ANN-S/PG or if Not Installed is selected,

the ANN-BUS Address Screen shown on the previous page will be displayed following the module
selection. The options selected for each of these modules will be the same for all modules of the
same type (refer to “ANN-S/PG (Print) Options Screen” on page 104 and “ANN-80 Options
Screen” on page 105
).